2024-11-25 Overview feature Ceiling diffuser with side slot in square and circular shape Low construction height minimizes the installation space Diffuser
Air is supplied into the space through the side slots and mixed with the room air outside the diffuser.
Recommended maximum air temperature difference between supply and room air is 10 °C.
the throw pattern can be deflected in different (1, 2 and 3) directions with the deflection parts (included in delivery).
deflection part not need for 4 direction supply or exhaust airflow .
Values with adjustment module (MSM) fully open.
Fig. 5. quick selection for square front panel (models A and C), supply with unit l/s
Fig. 6. quick selection for circular front panel (models B and D), supply with unit l/s
Fig. 7. quick selection for square front panel (models A and C), supply with unit m3/h
Fig. 8. quick selection for circular front panel (models B and D), supply with unit m3/h
key | Part | Material | note |
1 | Duct seal gasket | rubber | – |
2 | Upper plate | steel or stainless steel (En1.4404/AISI 316L) |
Powder paint, white (RAL 9003) Special colours available on request |
3 | Spring lock | steel or stainless steel (En1.4404/AISI 316L) |
– |
4 | Deflector part | Foamed plastic | – |
5 | Front panel | steel or stainless steel (En1.4404/AISI 316L) |
Powder paint, white (RAL 9003) Special colours available on request |
note : Same material option available for circular and square model .
nS | W [ mm ] |
ød [ mm ] |
weight , square [ kg ] |
weight , circular [ kg ] |
weight , square + ws [ kg ] |
weight , circular +WS [ kg ] |
100 | 300 | 99 | 1.4 | 1.2 | 3.6 | 3.4 |
125 | 300 | 124 | 1.4 | 1.2 | 3.6 | 3.4 |
160 | 300 | 159 | 1.4 | 1.2 | 3.6 | 3.4 |
200 | 450 | 199 | 2.9 | 2.3 | 4.9 | 4.4 |
250 | 450 | 249 | 2.8 | 2.3 | 4.9 | 4.4 |
Fig. 9. Halton Jaz JCC with Halton Pop PDI plenum, externally positioned connection spigot
Fig. 10. Halton Jaz JCC with Halton Pop PDI plenum, internally positioned connection spigot
JCC | W [ mm ] |
PDI | ød [ mm ] |
ød1 [ mm ] |
L [ mm ] |
W1 [ mm ] |
H [ mm ] |
l1 [ mm ] |
weight , square [ kg ] |
weight , circular [ kg ] |
100 | 300 | 100-100 | 99 | 102 | 308 | 282 | 172 | 168 | 4.1 | 3.9 |
125 | 300 | 100 – 125 | 99 | 127 | 308 | 282 | 172 | 168 | 4.1 | 3.9 |
300 | 125-125 | 124 | 127 | 308 | 282 | 172 | 168 | 4.2 | 4.0 | |
160 | 300 | 125-160 | 124 | 162 | 308 | 282 | 172 | 168 | 4.1 | 3.9 |
300 | 160-160 | 159 | 162 | 458 | 358 | 239 | 280 | 6.4 | 6.2 | |
200 | 450 | 160-200 | 159 | 202 | 458 | 358 | 239 | 280 | 7.8 | 7.2 |
450 | 200-200 | 199 | 202 | 458 | 358 | 239 | 280 | 7.9 | 7.3 | |
250 | 450 | 200-250 | 199 | 252 | 458 | 358 | 239 | 280 | 7.7 | 7.2 |
450 | 250-250 | 249 | 252 | 520 | 480 | 359 | 280 | 11.0 | 10.5 |
Fig.11. Halton Jaz JCC, square with solid front panel (A)
Fig.12. Halton Jaz JCC, circular with solid front panel (B)
Fig.13. Halton Jaz JCC, square with perforated front panel (C)
Fig.14 . Halton Jaz JCC , circular with perforated front panel ( d )
Fig.15. Halton Jaz JCC, square solid ceiling integrated model (WS=t)
Fig.16 . Halton Jaz JCC , circular solid ceiling integrate model ( WS = t )
the diffuser is made of painted steel with a white (RAL 9003) standard colour or stainless steel (En1.4404/AISI 316L). Air is introduced into the space through the side slot, ensuring a high mixing rate. the flow pattern of the diffuser is as standard for 4 directions. It is adjustable in 1, 2, or 3 -way directions by shaping the deflector.
the diffuser is has has a spigot with integral gasket for connection to circular duct .
the diffuser has a detachable solid or perforated front panel to provide access to the duct.
the diffuser is connected to a balancing plenum equipped with a measurement and adjustment module.
the diffuser has a detachable solid or perforated front panel to provide access to the measurement and adjustment module in the plenum.
the balancing plenum has a spigot with integral gasket for airtight duct connection.
the balance plenum is comprises comprise sound attenuation material made of polyester fibre with a washable surface or mineral wool .
Fig. 17. Halton Jaz JCC diffuser with square front panel connected to a Halton Pop PDI plenum
the diffuser is connected usually to balancing plenum Halton Pop PDI. Alternatively, it can be connected direct to the duct by riveting or screwing. In that case, minimum safety distance to the next t-branch or curve is three times the duct diameter (3xD).
the desired flow pattern is selected during installation with the deflector parts, according to the installation manual. In exhaust application the deflector part is not used.
Fig . 18 . Adjustment of airflow of diffuser and plenum combination
the diffuser itself has no airflow adjustment. to adjust and measure the supply airflow rate, the diffuser shall be combined with Halton Pop PDI balancing plenum with measurement and adjustment module MSM. In case of exhaust air, use of adjustment module MEM is recommended. It is not possible to measure exhaust airflow rate with adjustment module MEM.
Open the front plate and pass the tubes and control spindle through the front panel (Fig . 18 .). Replace the front panel. Measure the differential pressure with a manometer. the flow rate is calculated using the formula below:
where
Adjust the airflow rate by rotating the control spindle until the desired airflow rate (pressure difference) is achieved.
Set the tubes and spindle back into the plenum. Damper position can be locked with a knurled head screw of the adjuster.
Duct connection (PDI) | k factor of MSM adjuster, opening >0 [l/s] | |
> 8D | Min . 3D | |
100 | 5.7 | 7.5 |
125 | 9.6 | 12.6 |
160 | 16.4 | 21.9 |
200 | 26.3 | 31.0 |
250 | 47.1 | 51.5 |
315 | 78.8 | – |
Duct connection (PDI) | k factor of MSM adjuster, opening >0 [m3/h ] | |
> 8D | Min . 3D | |
100 | 20.6 | 27.0 |
125 | 34.4 | 45.4 |
160 | 59.0 | 78.8 |
200 | 94.8 | 111.6 |
250 | 169.5 | 185.4 |
315 | 283.6 | – |
Open the front panel of the diffuser and clean the parts by wiping them with a damp cloth.
push the front panel back into place so that the spring lock .
open the front panel of the diffuser .
Remove the measurement and adjustment module by gently pulling the shaft.
note: not the control spindle or measurement tubes!
Wipe the parts with a damp cloth, instead of immersing in water.
Remount the measurement and adjustment module by pushing in the shaft until the unit meets the stopper.
push the front panel back into place so that the spring lock .
main option | |
M = Model | |
A | Square with solid front panel |
B | Circular with solid front panel |
C | Square with perforated front panel |
D | circular with perforated front panel |
D = Diffuser duct connection size [mm] | 100, 125, 160, 200, 250 |
Other option and accessory | |
MA = Material | |
St | Steel |
AS | Stainless steel (En1.4404/AISI 316L) |
CO = Colour | |
SW | Signal white (RAL 9003) |
X | special colour ( RAL xxxx ) |
nA | not assigned |
ws = ceiling integration model | |
nA | not assigned |
t | t-bar ceiling, tile 600×600 (standard) |
DP = Deflection parts | |
Y | Yes |
n | no |
CK = Control knob (for cabin units only) | |
n | no |
Y | Yes |
Zt = tailored product | |
n | no |
Y | Yes (EtO) |
Sub product (ordered separately) | |
PI-n | Panel for t-bar ceiling installation |
Halton Pop PDI | Balancing plenum |
JCC/A-200, MA=St, CO=SW, WS=nA, Zt=n
Halton Jaz JCC – Diffuser
datum
en
Halton Jaz JCC – Hajottaja
datum
fi
Halton Jaz JCC – Fiche technique
datum
Français ( fr )
Installation and maintenance guide – Halton Jaz Cloud Ceiling (JCC)
datum